Digital ManoMeter for the examination of cooling systems
{{details.product.PriceUnits}}
Please fill out this field...
Please enter a number...
Please enter at least 1...
Please enter at max 999999...

You purchased this item on {{details.product.OrderHistory[0].OrderDate | date : 'yyyy-MM-dd'}}

The dV-2 Cool was designed for monitoring tasks at refrigerators and refrigerating plants. Vapour pressure/temperature graphs for 5 refrigerants are saved in the unit and can be selected by pressing a button.

At the touch of a button, the battery-driven instrument switches the LCD-display between vapour temperature and pressure indication, with the display offering a choice of bar / °C or PSI / °F.

The high resolution display means that dV-2 Cool can also be used for measuring leaks in vacuums.

The rugged dV-2 Cool with a stainless steel pressure sensor can optionally be fitted with a protective rubber covering. The face of the instrument can be rotated towards the pressure connection, thus allowing the ideal alignment of the display when fixing the instrument.

The dV-2 Cool has the following functions:

GAS : Selection of the refrigerant.

UNITS : Switching between bar / °C and PSI / °F

CONT : The instrument turns off 15 minutes after the last key function. Activating CONT (Continuous) deactivates this automatic turn-off.

BAT LOW : The battery symbol illuminates when battery power is low.

Refrigerant:
In the standard version, the vapour pressure/temperature graphs of the following refrigerants are stored:
R22, R12, R507, R404a, R134a.
Other refrigerants optionally available (on request).

 

 

  • Pressure Ranges : -1…40 to -1…80 bar
  • Accuracy: ±0,1 %FS
  • Total Error Band: ±0,1 %FS @ 0…50 °C
  • Special Characteristics: Stored vapour pressure curves
  • Interfaces: None
  • Display: 5-digit LCD display

Pressure Ranges

-1...40 bar | -1...80 bar

Display-Resolution

1 mbar | 2 mbar

Overpressure

1,5 x pressure range

Accuracy *

0,1 %FS

Compensated Temperature Range

0...50 °C

Storage- / Operating Temperature

-10...60 °C / 0...50 °C

Display- / Measuring Interval

2 x per second

Supply

3 V battery, type CR 2032

Battery Life

≈ 2 months at continuous operation

Pressure Connection

7/16 UNF. Optional: other connections.

Protection

IP 64

Width x Height x Depth

68 x 70 x 35 mm

Weight

≈ 90 g (with rubber protection ≈ 126 g)

Optional Accessories

  • Protective rubber covering
  • Front display with customer logo

* Includes linearity, repeatability, hysteresis and temperature error. Does not include Zero stability.