Instrotech Application : RS485 DIGIBUS

This application note describes how to setup a RS485 bus using the digibus protocol

  • The instruments to be used must be ordered with an RS485 option
  • Each instrument must be set to a different address BEFORE connection to the bus
  • The instruments and the computer must use the same baud
  • The Ascii bus menu must be off on all instruments

SMART CONVERTER
The A53 converts RS232 from a computer into RS485 for the bus. This converter is SMART as is changes the RS485 to transmit whenever a message is sent by the computer. No handshaking line RTS is required and no software is needed.

Setup

  • Open the converter and set DIP switch
  • SW1 is on for RS485 mode
  • SW2 is on for automatic handshaking
  • Insert JP1 for the end of bus terminator 120 ohms
  • Wire 9 to 30 volts dc to terminal 6 - and 7 +
  • Turn on the power: the CTS and power leds come on
  • Plug in the RJ45 cable from the RS232 connector to the computer
  • Wire terminal 1 TXD+B to the instruments D+, all in parallel
  • Wire terminal 2 TXD-A to the instruments D-, all in parallel
  • To extend the RS232 cable connect white to pin 5 0v, green to pin 3 tx, blue to pin 2 rx : dsub 9 female

Network Test
To test the network with the DOS DIGIBUS.EXE program

  • Run the program
  • Type in the COM number 0 to 1 = port 1 to 2
  • Type in the unit number of the instrument
  • Type in the register number eg 8C, 4001 process display
  • The program will show you the string sent
  • The program will show you the string received
  • The program will show you the result

PROTOCOL
Digibus protocol document


Software Test
To test your computer / cable
  • Plug an rs232 cable between the two RS232 ports on your computer
  • Run the DIGIREM.EXE program, setup for COM0
  • Run the DIGIBUS.EXE program on COM1
To test the software written by you
  • Once you see how this works, quit the digibus program
  • Test your program on COM1 and watch the result
Terminator
If there are a lot of communication errors this can be cause by reflections at the two ends of the bus. This is corrected by putting a resistor between D+ and D- at each end.

Distance Resistor
1200M 110 ohm
600M 220 ohm
300M 330 ohm

If this does not work then lower the BAUD rate