{{image.AltTag}} {{image.AltTag}}
Default Image Default Image

{{details.product.ModelName}}

Sku: {{details.product.ModelNumber}}

5.5-digit gray od/binary or digit BCD indicator
{{details.product.PriceUnits}}
Please fill out this field...
Please enter a number...
Please enter at least 1...
Please enter at max 999999...

You purchased this item on {{details.product.OrderHistory[0].OrderDate | date : 'yyyy-MM-dd'}}

As a universal indicator, the instrument is fully programmable from the front push buttons for decimal point selection, scaling, positive or negative logic, parallel or multiplexed BCD input, Gray Code input & Binary input. The panel mount housing is a standard DIN 48mm x 96mm size.
Applications include displays for PLC outputs for process control, & displays for absolute shaft encoders.
Options include programmable analogue output, one, two, three or four alarms, RS-232 output etc. The analogue output is programmable from the front push buttons.
Selected options now feature ‘Plug & Play’ technology, allowing option boards to be ordered separately & field fitted when required.

  • Front panel IP 65 / NEMA 4 / UL Type 4 rating,
  • 5 ¾ digit display with parallel BCD input (-199999 to 799999)
  • 6 digit display with multiplexed BCD input (-199999 to 999999) 999999)
  • Positive or negative (true or inverse) logic
  • 5 to 24V logic levels
  • Keypad lockout as standard
  • Low cost - high performance design
  • Keypad lockout available at no extra charge
  • Meets European EMC directive 89/336/EEC & Low Voltage directive 73/23/EEC
  • Customizable to suit your requirements

General

Display 4 digit : -1999 to 9999
Display Colour : Red
Display Size : 14.2mm
Display Type : 7 Segments LED
Enviromental Humidity : < 85% non-condensing
Enviromental Operating temperature range : -10 to +50°C
Enviromental Service temperature range : -15 to +60°C
Enviromental Storage temperature range : -40 to +80°C
Front panel rating IP 65 / NEMA 4 / UL Type 4 with supplied o-ring seal
Mounting Panel Mounted
Physical Cut out Size : 48mm x 96mm
Physical Size : 48mm x 96mm x 147mm
Physical Weight : approx. 385g (no options fitted)
Power Supply 12Vdc or 24Vdc non-isolated on request, 5VA typical
Power Supply Optional : 12Vdc isolated switch mode power supply option (Option 3008-12), 5VA typical
Power Supply Optional : 24Vdcsolated switch mode power supply option (Option 3008-24), 5VA typical
Power Supply Optional : 8 - 30Vdc isolated switch mode power supply option (Option 3008), 5VA typical 95V-265Vac/dc switch mode power supply option (Option 3010), 5VA typical
Power Supply Optional : 95V-265Vac/dc switch mode power supply option (Option 3010), 5VA typical
Power Supply Standard : 115 / 230 VAC ± 10% (standard), link selectable, 50/60Hz, 5VA typical
Protection UL94V-0 : Flame retardant ABS plastic housing
Regulatory compliance Complies with EC Directives 89/336/EEC & 73/23/EEC
Regulatory compliance Complies with EC Directives 89/336/EEC & 73/23/EEC

Set Point Options

Electro-mechanical relay: Form type: Form C (change-over contact)
Electro-mechanical relay: Rating: 250Vac, 30Vdc, 2A, power factor 1
Solid-state relay Form type Form A (normally open contact)
Solid-state relay Rating: 400Vac/dc, 0.5A, power factor 1

Serial Interface Options

Capabilities - Asciibus protocol - continuous output approximately 5 x second  
Capabilities - Asciibus protocol - continuous output approximately 5 x second - output on demand via print button
Capabilities - Asciibus protocol - continuous output approximately 5 x second - output on demand via serial request
Capabilities - Digibus protocol Full remote control, except for field setup
Isolation to input Optional, 1500V isolation (order option 3006)
Serial interface RS-232 or RS-485, 2400, 4800, 9600 & 19200 baud

Operation

Display specification 6 digit (-199999 to 999999) bright red LED, 14.2mm high
Display update rate 5 per second
Input types Parallel or multiplexed BCD, Gray Code, or Binary input
Internal pull-ups Yes
Level 5 to 24V
Logic Positive or negative (true or inverse)
Memory retention Full non-volatile operation
Setup and calibration Full digital with visual prompting in plain messages
Terminations 2 way plug for auxiliary supply, 0.2 - 2.5mm
Terminations 25 way D-type male connector, with female cable plug incl.
Warm-up time None required

Analogue Outout Options

Analog output accuracy 0.1% of full scale, 12-bits
Analog output isolation Optional, 1500V input/output isolation (order option 3006)
Analog output temp. coefficient 20ppm / °C typically
Current analog output load 500O maximum (current is source, not sink)
Voltage analog output load 1kO minimum
  • DPM3003 - 0 - 20mA / 4 - 20 mA analogue output
  • DPM3006 - Isolated outputs (order with 3002/3/13)
  • DPM3009 - Parallel BCD output (cannot be ordered with any alarm options, option 3006 or with option 3022)
  • DPM3028 - 10 - 30Vdc non isolated dc supply
  • Setpoint - Alarms - DPM3001P, DPM3001M, DPM3004P, DPM3004M, DPM3017P, DPM3017M, DPM3018P, DPM3018M
  • Outputs - DPM3002, DPM3013
  • Power Supply - DPM3008, DPM3010
  • Displays - DPM3020

For more information, click here.

Download DPM5002 Datasheet